TECHNICAL SPECIFICATIONS
| UPS BLUE-AP 10000 | UPS BLUE-AP 20000 | UPS BLUE-AP 30000 | UPS BLUE-CB 40000 | |
| POWER |
||||
| VA/W | 10.000VA/9.000W | 20.000VA/18.000W | 30.000VA/27.000W | 40.000VA/36.000W |
| INPUT |
||||
| Phase | Triphase + Ground | |||
| Voltage (Vac) | 380 / 400 / 415 | |||
| Voltage Range (V) | 240-320 / 480 | |||
| Frequency (Hz) | 50 / 60 ±10% | |||
| Input current distortion | †5% | †3% | ||
| Power factor | > 0.99 | |||
| OUTPUT | ||||
| Phase | Triphase + Ground | |||
| Voltage (V) | 380 / 400 / 415 | |||
| Static voltage variation | ±1% | |||
| Wave form | Sinusoidal | |||
| Armonic distortion | THD<= 2% linear load, THD<= 5% not linear load | |||
| Frequency | 45~55Hz / 54~66Hz Synchronized |
|||
| 50/60 ±0.05Hz From battery | ||||
| Peak factor | 3:1 max | |||
| Overcharge capacity | 60 min to 110%, 10 min to 125%, 1 min to 150%, 150ms over 150% | 10 min to 110%, 1 min to 133%, 5s to 150%, 500ms over 150% | ||
| Outlet | Terminal block | |||
| TRASFER TIME |
||||
| Assenza rete | Zero | |||
| Inverter / Bypass | 4ms | |||
| ECO / Inverter | <3ms | |||
| EFFICIENCY |
||||
| On line mode | 94%@ full load (>98% in Eco Mode) | |||
| Battery mode | >92% | |||
| BATTERY | ||||
| Type | 12V Sealed acid | |||
| Standard back up time* | /10, /15, /30, /60 | /10, /20, /30, /60 | /10, /15, /30, /60 | /10, /20 |
| Charge | 6-12 h depending on the charge settings | |||
| INDICATIONS | ||||
| Display LCD | Indicates the operating status and parameters of the UPS | |||
| OTHER FEATURES |
||||
| Parallel function | Included | |||
| DIMENSIONS |
||||
| (LxPxH) mm | 500x706x960 | 500x706x1230 | 440x850x1320 | |
| WEIGHT | ||||
| Peso netto | 151kg | 239kg | 261kg | 595kg |
| ENVIRONMENT | ||||
| Temperature | 0~40°C / 20~90% | |||
| Noise | <55dB @ 1m | |||
| INTERFACE | ||||
| USB/RS232 | Windows, MAC (Linux, IBM Aix, Sun Solaris, FreeBSD) | |||
| Slot options | Internal: SNMP / AS400 | |||
| SOFTWARE |
||||
| Included | UPS Monitor & PC Shutdown | |||
| EMERGENCY POWER OFF |
||||
| Epo | Included | |||
| PROTECTIONS |
||||
| Included | Overcharge, short circuit, over temperature | |||